Airtech Pty Ltd
attn. Barry Machin
971 South Road
Melrose Park SA 5039
1 December 1998
Dear Barry,
As discussed on the phone yesterday, I'm attaching a plan of the new part of the
house with sufficient of the old plan to enable you to relate its position. We
plan to use the existing unit for cooling only in the extension. We appreciate
that there may be a problem cooling the entire house with the current unit, but
on the other hand we note that at no time in the last summer did the temperature
in the house exceed 27° without air conditioning. The biggest problem I see
will be keeping the back part of the extension cool without more sophisticated
control methods. In this connection, I would ask you to ensure that the dampers
are capable of frequent opening and closing while the unit is operating.
.P
In addition, I remind you of the following still unresolved problems:
-
The existing ductwork appears to be incorrectly laid. The two bedrooms at the
extreme bottom left of the current plan are connected by a single relatively
long and thin duct, whereas the study is connected by a shorter and wider one.
Similar considerations apply for the laundry, which appears to have too short
and wide a duct. This would completely explain the problems we have with the
study and laundry being too warm.
-
The thermostat is not operating correctly. Although it was adjusted last
winter, the cut-in and cut-out temperatures appear to have diverged and are now
about 3.2° apart.
-
In addition, when cooling, the unit does not stop cooling when it reaches the
target temperature. Recently, when the outside temperature was about 32° and
the inside temperature was about 24°, I turned the unit on to cool to 22°.
After it reached 20.5°, I changed the required temperature to 29°, but it
continued cooling.
-
The cover of the thermostat does not close. This appears to be due to faulty
construction: we can't see any damage done to it, and it barely shut from the
beginning.
-
We still do not have a satisfactory resolution to the icing problem. As I
explained, I believe that a lot of the problem is due to the way the external
unit was mounted: it was pointing into the weather (West), and the winds can be
very high in this area. I believe that the last case of icing was caused by a
combination of wind, which reduced the effectiveness of the fans, and rain which
landed directly on the cooler, thus causing the icing.
As you can see from the plan, we will be building an open carport over the area
where the external unit is located. I believe that this will solve the problem,
but we will not know this until next winter. If you are agreed, we can postpone
this point until the winter, under the understanding that if there still is
icing next winter, you will address the issue. Please confirm that you agree to
this approach.
We agreed that you would get the manufacturer to look at the thermostat issues
in the immediate future.
Sincerely,
Greg Lehey